MC-Basic:IDNSTRING

From SoftMC-Wiki
Revision as of 09:19, 22 May 2014 by Miborich (talk | contribs)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to: navigation, search

This function is used to read the value of a specified element of an IDN from a specified drive. It should be used when reading an IDN that takes string values.

Short form

Istr

Syntax

?IdnString (<drive address>, <IDN>, <element>)

Availability

All versions

Range

<drive address>: 1 to 254
<IDN>: 1 to 65535
<element>: 1 to 7

Scope

Configuration, Task or Terminal

Limitations

  • Read only
  • Executed only in SERCOS communication phases 2, 3 and 4
  • Not supported in EtherCAT system

Examples

?IdnString(1, 95, 7)                                     ‘Get diagnostic message from drive

See Also