This flag indicates whether a table is monotonic. Only the monotonicity of the master data is relevant.

The monotonicity of a table is checked when:

  • Data is loaded using the LOADCAMDATA command
  • The function CHECKCAMMONOTONIC() is executed
  • Camming is engaged by setting the Slave property to the value 2.

The cam tables must be monotonic in order to be used.

Short form

Imon

Syntax

?<cam>.IsMonotonic

Availability

All versions

Type

Long

Range

0 or 1

Scope

Configuration, Task or Terminal

Examples

?Cam1.Imon