Difference between revisions of "MC-Basic:cam.ISMONOTONIC"

From SoftMC-Wiki
Jump to: navigation, search
Line 42: Line 42:
 
|SEE ALSO=
 
|SEE ALSO=
 
* [[MC-Basic:CHECKCAMMONOTONIC|CHECKCAMMONOTONIC]]
 
* [[MC-Basic:CHECKCAMMONOTONIC|CHECKCAMMONOTONIC]]
* [[Axystems:MC-Basic:CREATECAMDATA|CREATECAMDATA]]
+
* [[MC-Basic:CREATECAMDATA|CREATECAMDATA]]
 
* [[Axystems:MC-Basic:LOADCAMDATA|LOADCAMDATA]]
 
* [[Axystems:MC-Basic:LOADCAMDATA|LOADCAMDATA]]
  
  
 
}}
 
}}

Revision as of 08:37, 22 May 2014

This flag indicates whether a table is monotonic. Only the monotonicity of the master data is relevant.

The monotonicity of a table is checked when:

  • Data is loaded using the LOADCAMDATA command
  • The function CHECKCAMMONOTONIC() is executed
  • Camming is engaged by setting the Slave property to the value 2.

The cam tables must be monotonic in order to be used.

Short form

Imon

Syntax

?<cam>.IsMonotonic

Availability

All versions

Type

Long

Range

0 or 1

Scope

Configuration, Task or Terminal

Examples

?Cam1.Imon

See Also