<pre> | <pre> | ||
CreatePLSData 4 MyPLS | CreatePLSData 4 MyPLS | ||
− | |||
<nowiki>MyPLS.PLSPosition[1] = 1000</nowiki> | <nowiki>MyPLS.PLSPosition[1] = 1000</nowiki> | ||
− | |||
<nowiki>MyPLS.PLSPosition[2] = 1100</nowiki> | <nowiki>MyPLS.PLSPosition[2] = 1100</nowiki> | ||
</pre> | </pre> | ||
+ | |||
As a short form, you can use '''PPOS''' in place of '''PLSPOSITION''': | As a short form, you can use '''PPOS''' in place of '''PLSPOSITION''': | ||
<pre> | <pre> | ||
<nowiki>MyPLS.Ppos[3] = 2000</nowiki> | <nowiki>MyPLS.Ppos[3] = 2000</nowiki> | ||
− | |||
<nowiki>MyPLS.Ppos[4] = 2200</nowiki> | <nowiki>MyPLS.Ppos[4] = 2200</nowiki> | ||
</pre> | </pre> | ||
+ | |||
You cannot change PLS positions when the PLS is enabled. Position values must be increasing monotonically. | You cannot change PLS positions when the PLS is enabled. Position values must be increasing monotonically. | ||
Line 155: | Line 154: | ||
MyPLS.PLSPolarity = ON | MyPLS.PLSPolarity = ON | ||
</pre> | </pre> | ||
+ | |||
Change '''PLSPOLARITY''' only if the PLS is disabled. | Change '''PLSPOLARITY''' only if the PLS is disabled. | ||
Line 163: | Line 163: | ||
MyPLS.PLSRepeat = 10000 | MyPLS.PLSRepeat = 10000 | ||
</pre> | </pre> | ||
+ | |||
'''PLSREPEAT''' defaults to 0, indicating that there is no repetition. Change '''PLSREPEAT''' only when the PLS is disabled. | '''PLSREPEAT''' defaults to 0, indicating that there is no repetition. Change '''PLSREPEAT''' only when the PLS is disabled. | ||
Revision as of 13:59, 26 March 2014
The softMC provides numerous types of I/O. It includes more than 40 I/O points as standard plus the drive includes 5 I/O points per drive. In addition, you can input an external encoder through any drive. The I/O can be extended to include PC104 cards from a variety of suppliers.
Contents
Local I/O SERCOS version of softMC
The softMC includes 23 inputs and 20 outputs as standard on the softMC. These are accessed with the system properties DIN.1 through DIN.23 and DOUT.1 through DOUT.20: For information concerning the properties of the signals that connect to these inputs and outputs, refer to the MC Installation Manual.
? System.Din.1 System.Dout.5 = System.Din1 ?System.Din System.Dout=0xfe
Local I/O softMC
softMC (CANOpen and EtherCAT) does not have local I/O. For backward compatibility sys.din.1 to sys.din.23 and sys.dout.1 to sys.dout.20 can be read and written but do not have any function.
Software I/O SERCOS version of softMC
The softMC provides virtual software I/O in addition to the standard I/O. The primary purpose of software I/O is to place a large group of I/O where it can be read from and written to as blocks in the softMC's dual port RAM. Virtual inputs are delivered from the host over DPRAM where virtual outputs are stored in the DPRAM and retrieved by the host. This is much faster than reading or writing individual I/O points one at a time. This allows efficient communication between a machine controller, such as a VB program or a software PLC, and the softMC program. For more information about virtual software I/O, refer to the MC API Manual.
Software I/O softMC
Not available
Bit-oriented Software I/O
Software I/O is used in the softMC program just like standard I/O. Standard inputs are accessed with SYSTEM.DIN.1 through DIN.23, and virtual inputs are accessed with SYSTEM.VIN.1 through VIN.32. Standard outputs are accessed with SYSTEM.DOUT.1 through DOUT.20, and virtual outputs are accessed with SYSTEM.VOUT.1 through VOUT.32. You can use software I/O to start events just as with standard I/O. Programmable limit switches can use software outputs just as with standard outputs. Here is an example:
OnEvent SoftwareInputEvent System.VIn.1 = ON System.VOut.1 = OFF If(System.VOut.4 = ON) . . .
Long-Word-Oriented Software I/O
The entire word (32 bits) of software input and output is accessed when a bit position is not included in the reference to the input or output variable. So the following statement is valid:
System.VOut=System.VIn
This statement copies the virtual software input to the output. The physical input and output variables are used in this manner. Be careful when assigning virtual I/O to physical I/O because there are fewer physical bits than there are virtual bits. There are only 20 bits of physical output, but the virtual output variable can have 32 bits.
PLS (Programmable Limit Switch)
A Programmable Limit Switch (PLS) monitors position feedback on any axis, real or simulated. A PLS offers more flexibility than a limit switch, as it allows many trip points and can be reconfigured on-the-fly. A PLS toggles the state of a specified system output when an axis position reaches any of the defined positions of the PLS. Some of the features of a PLS are:
- Multiple position specifications.
- Multiple PLSs per axis
- PLS pattern repetition
- Position hysteresis
- Enabling and disabling of PLSs
- The system output may be digital or soft (fast data)
PLS positions are defined in an array that allows you to change individual values of PLS positions. This array must be increasing monotonic. There is no limit of the number of positions or PLSs that can be defined.
The initial output polarity is specified with PLSPOLARITY. The output state is set when the PLS is enabled.
Enable and Disable
After being defined, a PLS is disabled (output pattern is not generated). The output is set when the PLS is enabled. The output is set to the defined initial state.
PLS properties are changed only when the PLS is disabled. Each enabled PLS requires CPU resources. Conserve those resources by disabling the unused PLS(s). PLSENABLE controls the status of the PLS:
MyPLS.PlsEnable = ON | OFF
PLSENABLE queries the status of a PLS:
?MyPls.PlsEnable if(MyPLS.PlsEnable = OFF) . . .
or drives events:
EventOn MyEvent MyPLS.PlsOutput = ON
Switch Positions
The basic mechanism of the PLS is the switch position(s) where the PLS output changes state. The figure belows shows a PLS output with one switch position at 100.
More switch positions can be added. To have the PLS in the above example turn back off at 200, simply add a second position at 200 as shown below:
You can add any number of positions. For example, to extend the above example to turn back on at 400 and off again at 600, add positions 3 and 4 as 400 and 600 as shown below:
There is no explicit limit to the number of positions you can have in a PLS, but the PLS positions must be increasing monotonic (Position2 must be greater than Position1, Position3 must be greater than Position2, etc.).
Repetition Interval
PLSREPEAT allows you to repeat the same PLS after a fixed number of counts. For example, the figure below shows a PLS that turns on at 0, off at 10 and has a PLSREPEAT value of 100:
Polarity
PLSPOLARITY allows you to control the polarity of the PLS output. The initial polarity may be specified as 1 or 0, indicating that the output is set to 1 or 0 after the PLS is enabled and when the axis is located between the first and second PLS positions. If the axis position (when the PLS is enabled) is not located within this segment, the output polarity is set to 0 or 1, according to the current position so that when the axis reaches the first segment, the output polarity is as indicated. The default value for polarity is 0.
Hysteresis
The softMC allows you to apply hysteresis around switch points. Hysteresis provides a margin in the switching between PLS positions to accommodate noise in the PLS axis. Set the hysteresis greater than the noise on the axis, (typically, 5 or 10 counts of encoder is sufficient, less is required for resolver systems). If you have a hysteresis of 0.01 position units, each transition of PLS position is moved forward 0.005 units for positive motion and backward 0.005 units for negative motion. If the axis driving the PLS is stopped directly on a PLS position and the inherent noise on the axis is less than the hysteresis, the PLS state does not change due to this noise.
Enable and Disable
PLSENABLE enables or disables the PLS(s). After being defined, a PLS is disabled. The output is fixed when the PLS is enabled. The PLS output is set to the defined initial state when the PLS is enabled.
PLS Output State
Query the digital output associated with the PLS to query the state of the PLS output. For example, assume the PLS output is assigned to SYSTEM.DOUT.1. To determine the output state of the PLS, query the state of SYSTEM.DOUT.1:
-->?Sys.Dout.1 0 | 1
Set Up
Step 1
Declare the PLS with Common Shared <var> as PLS in Config.Prg or at the terminal. You must name the PLS, specify the axis that drives the PLS, and name an output to be controlled by the PLS. For example:
Common Shared MyPLS as PLS A1 System.Dout.1
sets up MyPLS as a PLS driven by axis A1 connected to SYSTEM.DOUT.1. The output can be a digital output (SYSTEM.DOUT.1 through DOUT.20) or it can be one of the virtual outputs (SYSTEM.VOUT.1 through VOUT.32).
After the Common Shared <var> as PLS executes, the PLS is disabled. Properties of the PLS are set as:
- A single PLS position exists at 0.
- The initial output polarity is 1.
- PLSREPEAT is set to 0.
- The hysteresis is set to 0.
These properties may be set explicitly, as long as the PLS remains disabled. You can check which output is associated with a given PLS using PLSOUTPUT.
Step 2
Create the PLS data structure and define PLS positions. The number of defined positions is not explicitly limited. A call to CREATEPLSDATA creates an array of n positions that stores the position data. The array is 1-based and an error is generated if you attempt to access an index outside of the array bounds. For example:
CreatePLSData 4 MyPLS MyPLS.PLSPosition[1] = 1000 MyPLS.PLSPosition[2] = 1100
As a short form, you can use PPOS in place of PLSPOSITION:
MyPLS.Ppos[3] = 2000 MyPLS.Ppos[4] = 2200
You cannot change PLS positions when the PLS is enabled. Position values must be increasing monotonically.
Step 3
Set the polarity. PLSPOLARITY defaults to OFF, indicating the PLS state should be OFF after the first position. Change PLSPOLARITY to ON to invert the state.
MyPLS.PLSPolarity = ON
Change PLSPOLARITY only if the PLS is disabled.
Step 4
Set PLSREPEAT. If you want the PLS to repeat, set the value of PLSREPEAT to a non-zero, positive number. For example, to have the PLS repeat every 10,000 position units, enter:
MyPLS.PLSRepeat = 10000
PLSREPEAT defaults to 0, indicating that there is no repetition. Change PLSREPEAT only when the PLS is disabled.
Step 5
Set PLSHYSTERESIS, if the application requires it. Hysteresis is only necessary if the system does stop on or near a PLS position. Normally, a PLSHYSTERESIS of 5 or 10 counts of encoder (converted to position units) or 2 or 3 counts of resolver resolution is sufficient.
MyPLS.PLSHysteresis = 0.01
Step 6
Enable the PLS. Enter:
MyPLS.PLSEnable = ON
There are a few other PLS functions you may need:
Change Polarity The default output state of a PLS is 0. Change this initial state by modifying PLSPOLARITY.
MyPLS.PLSPolarity = 1
The PLS must be disabled when changing this setting.
Query the Name Query the name of the axis driving the PLS:
? MyPLS.PLSAxisName
returns the axis associated with the PLS (A1).
Disable the PLS Disable the PLS. For example:
MyPLS.PLSEnable = OFF
You must disable a PLS to change PLS properties. Disabling a PLS also helps conserve CPU resources.
Delete a PLS Delete a PLS to remove it from the system only when the PLS is disable and there are no tasks in memory. For example:
DeletePLS MyPLS
External Encoders
The softMC supports external encoders (encoders not connected to an axis controlled by the softMC). These encoders are connected to the system using the external encoder input of any drive in the system. You can access the encoder periodically with:
? IDNValue(<''axis''>.DriveAddress, 53, 7) ‘Query external encoder position
If you are using the encoder for master/slave operation or in a way that requires the value of the signal be updated to the softMC every SERCOS cycle, you must configure the telegram for that axis as Telegram type 7. You also must specify that external position must be included in the telegram. This command is only available when in communication phase of 2 or higher.
PC104
If you need more I/O than the 23 digital inputs and 20 digital outputs that the softMC provides, there is an optional PC104 bus. This lets you install PC104-compatible cards to provide additional I/O ports. Because the PC104 bus is an extension for the softMC, this configuration is often called a mezzanine bus.
The softMC supports the full PC104 mechanical specification for as many as two PC104 cards. Adding these cards generally increases, by one, the number of slots taken by the softMC. The softMC supports a subset of the electrical connections of PC104, but the subset is sufficient to accommodate nearly all PC104 I/O cards. Refer to the Installation Manual for more details concerning which pins are supported.
Configuring PC104 Cards
You must configure the PC104 cards for memory and I/O space. See the manufacturer’s manual for your particular PC104 card.
Memory Space :
All PC104 cards used on the softMC which are memory mapped, must be mapped into the softMC memory without causing conflict. If you are using two PC104 cards, you must be careful not to overlap the memory spaces of these cards.
I/O Space :
All PC104 cards used on the softMC which are I/O mapped, must be mapped between 0x100 to 0xFFFF. Address ranges: 0x300 through 0x3ff and 0x2f8 through 0x2ff are not available. If you are using two PC104 cards, you must be careful not to overlap the I/O spaces of these cards. Do not use ranges 0x300 through 0x3ff and 0x2f8 through 0x2ff, even though they are not protected by the software.
IRQ:
The softMC does not support interrupts from PC104 cards.
Installation
To install your PC104 card:
- Power down your unit.
- Always use proper static handling procedures.
- Mount the cards.
- Install stand-offs.
Commands
The softMC supports PC104 with memory and I/O instructions. For further information on these commands, refer to the MC Reference Manual.
If you are using memory-mapped PC104 cards, you will need the memory access commands, PEEK and POKE. The valid memory address range for PEEK is 0xA0000 through 0xDFFFF. The valid memory address range for POKE depends on the hardware version of the softMC card.
- For the ISA-Bus card, the valid memory address range for POKE is 0xA0000 to 0xCFFFF and 0xDA000 to 0xDFFFF.
- For the PCI card, the valid memory address range for POKE is 0xA0000 to 0xC7FFF and 0xDB000 to 0xDFFFF.
- PEEKB transfers byte-wide (8-bit) data from the PC104 memory bus to a variable.
- PEEKW transfers word-wide (16-bit) data from the PC104 memory bus to a variable.
- POKEB transfers byte-wide (8-bit) data to the PC104 memory bus.
- POKEW transfers word-wide (16-bit) data to the PC104 memory bus.
- If you are using I/O-mapped PC104 cards, you need INP and OUT.
- INPB transfers byte-wide (8-bit) data from the PC104 I/O bus to a variable.
- INPW transfers word-wide (16-bit) data from the PC104 I/O bus to a variable.
- OUTB transfers byte-wide (8-bit) data to the PC104 I/O bus.
- OUTW transfers word-wide (16-bit) data to the PC104 I/O bus.