Difference between revisions of "Modbus Communication API"

From SoftMC-Wiki
Jump to: navigation, search
 
(21 intermediate revisions by 2 users not shown)
Line 1: Line 1:
{{Languages|Modbus_Communication_API}}
+
<div class="noprint" id="BackToTop" style="background-color:; position:fixed; bottom:32px; left:95%; z-index:9999; padding:0; margin:0;">
<div id="BackToTop" class="noprint" style="background-color:; position:fixed; bottom:32px; left:95%; z-index:9999; padding:0; margin:0;">
+
&nbsp;
<span style="color:blue; font-size:8pt; font-face:verdana,sans-serif; border:0.2em outset:#ceebf7; padding:0.1em; font-weight:bolder; -moz-border-radius:8px; ">
+
<span style="color:blue; font-size:8pt; font-face:verdana,sans-serif; border:0.2em outset:#ceebf7; padding:0.1em; font-weight:bolder; -moz-border-radius:8px;">[[File:TOP2.png|50px|TOP2.png|link=#top]]</span></div>  
[[Image:TOP2.png|50px|link=#top]] </span></div>
+
A complete presentation can be found here:&nbsp;&nbsp;'''[http://softmc.servotronix.com/wiki/Modbus_Presentation Modbus_Presentation]'''
 +
 
 
== Overview ==
 
== Overview ==
 +
 
=== Basic Overview ===
 
=== Basic Overview ===
* This describes how to set up Modbus communication for the softMC, and how to generate softMC scripts to handle Modbus communication.
+
 
* It is assumed you are familiar with the principles of Modbus communication, although some of them will be described in this page.
+
*This describes how to set up Modbus communication for the softMC, and how to generate softMC scripts to handle Modbus communication.  
* It is also assumed your are familiar with the softMC, ControlStudio and MC-Basic programming.
+
*It is assumed you are familiar with the principles of Modbus communication, although some of them will be described in this page.  
 +
*It is also assumed your are familiar with the softMC, ControlStudio and MC-Basic programming.  
  
 
=== Modbus Communication Background ===
 
=== Modbus Communication Background ===
* A Motion Controller (MC) can act as a server (slave), a client (master) or both at the same time.
+
 
* Each MC connection (TCP/RTU) can be used either as a server component (if the connection is used by the MC’s server-side) or as a client component (if the connection is used by the MC’s client-side).
+
*A Motion Controller (MC) can act as a server (slave), a client (master) or both at the same time.  
* Each component has its own parameters that defines it.
+
*Each MC connection (TCP/RTU) can be used either as a server component (if the connection is used by the MC’s server-side) or as a client component (if the connection is used by the MC’s client-side).  
* When the MC acts as a server, all server components share the '''same''' memory address space, thus acting as one server with multiple connections.
+
*Each component has its own parameters that defines it.  
* Each server (slave) on a Modbus network has its own deviceID, which is a number between 1 and 247.
+
*When the MC acts as a server, all server components share the '''same''' memory address space, thus acting as one server with multiple connections.  
 +
*Each server (slave) on a Modbus network has its own deviceID, which is a number between 1 and 247.  
  
 
=== The Modbus server registers ===
 
=== The Modbus server registers ===
* There are 4 types of registers in the Modbus Server address space:
 
*# Bits (1-bit registers)
 
*# Input Bits (1-bit READ-ONLY registers)
 
*# Holding Registers (16-bit registers)
 
*# Input Registers (16-bit READ-ONLY registers)
 
* Servers can read and write their own address space.
 
* Clients can read and write a remote server’s address space.
 
 
  
 +
*There are 4 types of registers in the Modbus Server address space:
 +
*#Bits (1-bit registers)
 +
*#Input Bits (1-bit READ-ONLY registers)
 +
*#Holding Registers (16-bit registers)
 +
*#Input Registers (16-bit READ-ONLY registers) 
 +
*Servers can read and write their own address space.
 +
*Clients can read and write a remote server’s address space.
  
 +
&nbsp;
  
 
= Getting Started =
 
= Getting Started =
  
In order to get started in using the Modbus features:
+
In order to get started with Modbus features the following steps are required:
  
 
#Download the required files:&nbsp;[[Media:ModBus_Required_files_new.zip|Media:ModBus Required files new.zip]]  
 
#Download the required files:&nbsp;[[Media:ModBus_Required_files_new.zip|Media:ModBus Required files new.zip]]  
Line 432: Line 436:
 
[[File:modbus;newAPI-readwriteSummary.jpg|850px|modbus;newAPI-readwriteSummary.jpg]]
 
[[File:modbus;newAPI-readwriteSummary.jpg|850px|modbus;newAPI-readwriteSummary.jpg]]
  
=Modbus Configurator=
+
= Modbus Configurator =
 +
 
 
== Background ==
 
== Background ==
 +
 
=== General ===
 
=== General ===
 +
 
The Modbus Communication Scripts Generator ('''Modbus Configurator''') is a tool that allows you to map your softMC application variables to Modbus tags.
 
The Modbus Communication Scripts Generator ('''Modbus Configurator''') is a tool that allows you to map your softMC application variables to Modbus tags.
  
'''Note''': Tag access is defined from the HMI perspective. In other words:
+
'''Note''': Tag access is defined from the HMI perspective. In other words:
* '''Read Access''' variables are written by the softMC to the Modbus address space.
+
 
* '''Write Access''' variables are read by the softMC from the Modbus address space.
+
*'''Read Access''' variables are written by the softMC to the Modbus address space.  
 +
*'''Write Access''' variables are read by the softMC from the Modbus address space.  
 +
 
 +
You can define whether a variable has Read Access (meaning it is read by the HMI/PLC), or Write Access (meaning it is written by the HMI/PLC). Currently, it is not possible to define a variable as having both Read Access and Write Access. However, all Write Access variables can be written once by the softMC upon system startup by a special routine that is generated in HMIMBMAP.LIB (see section below).
 +
 
 +
The MC MBConfigurator creates three files:
 +
 
 +
*'''HMIMBMAP.LIB''' and '''HMIMBMAP.PRG''' files are MC-Basic scripts that are used to start a softMC task. These are default file names, which you can change, but must retain the 8.3 format. This task cyclically and indefinitely reads/writes Modbus tags according to access type.
 +
*A '''.CSV''' format file that can be used by an HMI development environment, such as '''JMobile Studio,'''&nbsp;'''Indusoft and HMIStudio''', to automatically import Modbus tags. You define the HMI development environment by selecting various Python scripts that will generate the .csv file.
 +
 
 +
== MBConfigurator setup ==
 +
 
 +
'''Note''': Variables destined to be mapped to Modbus tags must be defined as '''global''' variables by the "Common Shared" declaration.
 +
 
 +
1. In order to map the variables, the program must be loaded in the softMC.
 +
 
 +
2. Start the Modbus Configuration. From the ControlStudio toolbar, select&nbsp;'''Tools > Modbus Configurator'''.
 +
 
 +
&nbsp; &nbsp; The Modbus Configurator windows opens.
 +
 
 +
3. Select&nbsp;'''Connection > Connect'''.
 +
 
 +
The settings dialog box opens. Makes sure the correct MC IP and port are inserted:
 +
 
 +
[[File:MBconnection.jpg|RTENOTITLE]]
 +
 
 +
4. In the Modbus Configurator window select&nbsp;'''Modbus Comm. Settings.&nbsp;'''Choose "'''Generate a csv file to use with softMI'''". Make sure Refresh&nbsp;rate is&nbsp;10ms or higher.
 +
 
 +
[[File:MBconnection2.jpg|RTENOTITLE]]
 +
 
 +
&nbsp;
 +
 
 +
5. In the&nbsp;'''Registers'''&nbsp;tab, enter the amount of registers needed per type.
 +
 
 +
#Notice: The maximum register number is 65536.
 +
 
 +
&nbsp;
 +
 
 +
6. Select '''Connections''', click Add and select TCP communication type with port number 502.&nbsp;
 +
 
 +
[[File:MBconnection3.jpg|RTENOTITLE]]
 +
 
 +
6.&nbsp;
 +
 
 +
1. Once the Modbus Configurator is connected to softMC, a complete list of all the global variables will appear on the right side. '''Double-clicking''' on the variables will automatically map them to Modbus tags in consecutive order. The automatic Modbus address and data type are displayed in the table.
 +
 
 +
2. '''Veriable type''' can be changed by clicking&nbsp;on the register type. Bits are 1 bit registers. It can be used for triggering (Write) functions, such as enable/disable or&nbsp;reading various statuses (Read).&nbsp;Hregs are 16 bit registers which can be used for number input&nbsp;(Write), such as set velocity/position&nbsp;or reading values (Read), such as position feedback.&nbsp;
  
You can define whether a variable has Read Access, or Write Access. Currently, it is not possible to define a variable as having both Read Access and Write Access. However, all Write Access variables can be written once by the softMC upon system startup by a special routine that is generated in HMIMBMAP.LIB (see section below).
+
If a mapped variable is defined as CONST, its access type is automatically set to Read. In such instances the access type cannot be changed. Read Access variables are read only by the HMI; therefore the softMC only writes them to the Modbus address space.
  
The MCMBConfigurator creates three files:
+
A variable that is not defined as CONST automatically appears as Write Access. Double-click on the access type to toggle the variable between Read Access and Write Access, and thus determine whether the variable will be read or written by softMC.
* '''HMIMBMAP.LIB''' and '''HMIMBMAP.PRG''' files are MC-Basic scripts that are used to start a softMC task. These are default file names, which you can change, but must retain the 8.3 format. This task cyclically and indefinitely reads/writes Modbus tags according to access type.
 
* A '''.CSV''' format file that can be used by an HMI development environment, such as '''JMobile Studio''' or '''Indusoft''', to automatically import Modbus tags. You define the HMI development environment by selecting various Python scripts that will generate the .csv file.
 
=== Mapping Variables ===
 
* Variables destined to be mapped to Modbus tags must be defined as global variables by the '''common Shared''' declaration.
 
* In order to map the variables, the program must be loaded in the softMC.
 
  
== Getting Started ==
+
&nbsp;
#Start the Modbus Configurator: from the ControlStudio toolbar, select '''Tools > Modbus Configurator'''. The Modbus Configurator tool will appear.
 
#From the top menu, Select '''Connection > Setting'''.
 
#'''Enter the MC's IP and port''' (default connection port is 5001), then '''click OK'''.
 
# From the top menu, Select '''Connection > Connect'''.
 
# Configure the Modbus Address Space
 
## From the top menu, Select '''Modbus Comm. Settings'''.
 
## In the '''General''' tab, Select the appropriate python script.
 
## In the '''Registers''' tab, enter the amount of registers needed per type, and the registers offset (Optional).
 
##* Notice: The maximum register number is 65536.
 
## In the '''Connections''' tab, add the server connections (TCP/RTU).
 
## Click '''OK'''.
 
# Map your variables
 
#* Once the Modbus Configurator is connected to softMC it gets updated with the complete list of all the global variables. Double-clicking on variables automatically maps them to Modbus tags in consecutive order. The automatic Modbus address and data type are displayed in the table, along with the Modbus address space area in which the data will be stored (Default: Holding Registers).
 
#* If a mapped variable is '''defined as CONST''', its access type will automatically set to "Read". In such instances the access type cannot be changed. "Read Access variables are read only by the HMI; therefore the softMC only <u>writes</u> them to the Modbus address space.
 
#* If a mapped variable is '''not defined as CONST''', it automatically appears with "Write" Access. '''Double-click on the access type''' to toggle the variable between Read Access and Write Access, and thus determine whether the variable will be read or written by softMC.
 
  
[[File:softMC_Modbus_HMI_(4).png|600px]]
+
[[File:MB3onnection4.jpg|1000x600px|MB3onnection4.jpg]]
<br/>
+
 
<br/>
+
&nbsp;
 +
 
 +
== Generating and Using Scripts ==
  
==Generating and Using Scripts==
 
 
After you are done mapping variables and defining the access types, a snapshot of the current configuration must be saved in order to generate the Modbus-handling scripts.
 
After you are done mapping variables and defining the access types, a snapshot of the current configuration must be saved in order to generate the Modbus-handling scripts.
  
 
1. Click '''Files''', and then '''Save As'''.
 
1. Click '''Files''', and then '''Save As'''.
  
:The mapping is saved in an '''.mbas''' file.
+
:The mapping is saved in an '''.mbas''' file.  
  
:If you makes changes after saving the .mbas file, the MBAS file indicator in the status bar will light up.
+
:If you makes changes after saving the .mbas file, the MBAS file indicator in the status bar will light up.  
  
 
2. To generate the product files, click '''Generate'''.
 
2. To generate the product files, click '''Generate'''.
  
:The Log windows will display Success messages.
+
&nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp;&nbsp;The Log windows will display Success messages.
  
:The product files were created in the target folder you chose when saving the .mbas file.
+
&nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; 3 files will be generated:&nbsp;'''HMIMBMAP.LIB''',&nbsp;'''HMIMBMAP.PRG''', which will be used by the MC and&nbsp;'''STX_HMI.CSV''', which will be used by the HMI program.
  
:The files HMIMBMAP.LIB and HMIMBMAP.PRG will automatically open in ControlStudio.
+
3. The defult location of the files generation is located in ControlStudio installation folder:&nbsp;C:\Program Files (x86)\Servotronix\MBConfigurator
  
[[File:softMC_Modbus_HMI_(5).png|600px]]
+
&nbsp;[[File:MBvonnection5.jpg|1000x600px|MBvonnection5.jpg]]
  
 +
&nbsp;
  
==Using the Modbus-Handling Scripts==
+
== Using the Modbus-Handling Scripts ==
1. Using the ControlStudio File Manager, copy HMIMBMAP.LIB and HMIMBMAP.PRG to the softMC.
 
  
'''Note''': Before these files can be loaded and used, your application must be loaded, and all mapped variables must exist in the softMC memory.
+
1. Using the ControlStudio, copy HMIMBMAP.LIB and HMIMBMAP.PRG to the softMC as shown in&nbsp;[[Media:ModBussetup.jpg|Media:ModBussetup.jpg]]
  
[[File:softMC_Modbus_HMI_(6).png|600px]]
+
'''Note''': Before these files can be loaded and used, your application(s), which include all the global veriables&nbsp;must be loaded (all mapped variables must exist in the softMC memory).<br/> <br/> 2. Using the ControlStudio Terminal, load the library HMIMBMAP.LIB:
<br/>
 
<br/>
 
1. Using the ControlStudio Terminal, load the library HMIMBMAP.LIB:
 
 
<pre>Load HMIMBMAP.LIB</pre>
 
<pre>Load HMIMBMAP.LIB</pre>
  
:Since HMIMBMAP.PRG imports this library it must not be loaded globally. This code can be executed wherever is convenient.
+
:Since HMIMBMAP.PRG imports this library it must not be loaded globally. This code can be executed wherever is convenient.  
 
 
2. Verify that the library was loaded successfully:
 
  
 +
3. Verify that the library was loaded successfully:
 
<pre>?tasklist</pre>
 
<pre>?tasklist</pre>
  
3. Start the Modbus communication task by loading the program:
+
4. Start the Modbus communication task by loading the program:
 
 
 
<pre>Load HMIMBMAP.PRG</pre>
 
<pre>Load HMIMBMAP.PRG</pre>
  
 
HMIMBMAP.PRG is defined as '''Program Continue''', therefore it starts automatically after it is loaded and it does not require an explicit StartTask command.
 
HMIMBMAP.PRG is defined as '''Program Continue''', therefore it starts automatically after it is loaded and it does not require an explicit StartTask command.
  
Of course, HMIMBMAP.PRG can be loaded and executed only after HMIMBMAP.LIB is loaded. Therefore, you should add the following code to AUTOEXEC.PRG or wherever is convenient:
+
Of course, HMIMBMAP.PRG can be loaded and executed only '''after''' HMIMBMAP.LIB is loaded. Therefore, you should add the following code to AUTOEXEC.PRG or wherever is convenient:
 
<pre>Load HMIMBMAP.LIB
 
<pre>Load HMIMBMAP.LIB
Load HMIMBMAP.PRG
+
Load HMIMBMAP.PRG</pre>
</pre>
+
 
 +
&nbsp;
 +
 
 +
== HMIMBMAP.PRG Explained ==
  
==HMIMBMAP.PRG Explained==
+
HMIMBMAP.PRG code:
The code:
 
 
<pre>import HMIMBMAP.LIB
 
<pre>import HMIMBMAP.LIB
 
Program Continue
 
Program Continue
Line 538: Line 569:
 
The functions '''Read_Modbus_Registers''' and '''Write_Modbus_Registers''' are invoked cyclically and indefinitely. '''Read_Modbus_Registers''' reads all the tags that are written by the HMI/PLC and updates the '''Write Access''' variables with new values, while '''Write_Modbus_Registers''' does the opposite.
 
The functions '''Read_Modbus_Registers''' and '''Write_Modbus_Registers''' are invoked cyclically and indefinitely. '''Read_Modbus_Registers''' reads all the tags that are written by the HMI/PLC and updates the '''Write Access''' variables with new values, while '''Write_Modbus_Registers''' does the opposite.
  
=HMI IDEs and .CSV Files=
+
= HMI IDEs and .CSV Files =
 +
 
 
Each line in the .csv file generated by the MCMBConfigurator file holds data about a single variable, such as Modbus address or data type.
 
Each line in the .csv file generated by the MCMBConfigurator file holds data about a single variable, such as Modbus address or data type.
+
 
 
This data can be used by an HMI IDE to import Modbus tags and associate them with HMI functionality.
 
This data can be used by an HMI IDE to import Modbus tags and associate them with HMI functionality.
  
 
Different manufacturer IDEs use different .csv formatting; therefore, various Python scripts are used to create the specific .csv files suitable for a particular manufacturer IDE.
 
Different manufacturer IDEs use different .csv formatting; therefore, various Python scripts are used to create the specific .csv files suitable for a particular manufacturer IDE.
  
==JMobile Studio==
+
= HMI Programs =
Python script: '''JMobile_csv.py'''
 
 
 
Default target .csv file name: '''JMobile_HMI.csv''' (user-definable)
 
 
 
To import tags, perform the following procedure in JMobile Studio.
 
 
 
===Define Protocol===
 
1. In the ProjectView pane, select '''Protocols'''.
 
 
 
2. Click the blue '''+''' sign.
 
 
 
3. From the list, select Modbus TCP.
 
 
 
4. In the Modbus TCP configuration window, define:
 
 
 
:IP Address: Set the IP address of your softMC.
 
 
 
:PLC Models: Select '''Generic Modbus''' (0-based), meaning the softMC Modbus server starts addressing tags from 0.
 
 
 
:Click '''OK'''.
 
 
 
[[File:softMC_Modbus_HMI_(7).png|600px]]
 
<br/>
 
<br/>
 
===Import Tags===
 
1. In the ProjectView pane, select '''Tags'''.
 
 
 
2. From the list, select '''Modbus TCP''' protocol defined previously.
 
 
 
[[File:softMC_Modbus_HMI_(8).png|600px]]
 
<br/>
 
<br/>
 
3. Click the '''Import Tags''' button.
 
 
 
4. Open the generated file '''JMobile_HMI.csv'''.
 
 
 
[[File:softMC_Modbus_HMI_(9).png|600px]]
 
<br/>
 
<br/>
 
5. Select the tags you want to add to your project, and click the ''Import tags'' button.
 
 
 
[[File:softMC_Modbus_HMI_(10).png|600px]]
 
<br/>
 
<br/>
 
 
 
==AdvancedHMI==
 
AdvancedHMI is an open source project (http://www.advancedhmi.com/), which is downloaded as a Visual Basic project. You can then open the project, add widgets, compile, and run it.
 
 
 
[[File:softMC_Modbus_HMI_(11).png|600px]]
 
<br/>
 
<br/>
 
1. Drag and drop '''ModbusTCPCom''' into MainForm.vb [Design].
 
 
 
2. The driver appears the bottom of the screen (circled in green).
 
 
 
:Click the driver, and then use the Properties pane (circled in red) to setup the IP address of the Modbus server.
 
 
 
:For example, drag and drop DigitalPanelMeter and MomentaryButton into MainForm.vb [Design].
 
 
 
[[File:softMC_Modbus_HMI_(12).png|600px]]
 
<br/>
 
<br/>
 
3. For both widgets, use the Properties pane to set the Modbus address that is associated with the variables from the softMC application.
 
 
 
[[File:softMC_Modbus_HMI_(13).png|600px]]
 
<br/>
 
<br/>
 
'''Note''':
 
::MC Modbus server addressing starts from '''40000'''.
 
::AdvancedHMI Modbus client addressing starts from '''40001'''.
 
::Prefix the address with the letter '''L'''.
 
  
4. Save the project (Ctrl+S).
+
'''Note''': HMI Studio is the most commonly used program.
  
5. Build the project (Ctrl+Shift+B).
+
*[[softMI_HMI_Getting_started|HMI Studio]]
 +
*[[JMobile_studio|JMobile studio]]
 +
*[[AdvancedHMI|AdvancedHMI]]
  
6. Run the project (F5).
+
[[Category:Modbus Communication]]

Latest revision as of 16:13, 16 February 2020

 

TOP2.png

A complete presentation can be found here:  Modbus_Presentation

Contents

Overview

Basic Overview

  • This describes how to set up Modbus communication for the softMC, and how to generate softMC scripts to handle Modbus communication.
  • It is assumed you are familiar with the principles of Modbus communication, although some of them will be described in this page.
  • It is also assumed your are familiar with the softMC, ControlStudio and MC-Basic programming.

Modbus Communication Background

  • A Motion Controller (MC) can act as a server (slave), a client (master) or both at the same time.
  • Each MC connection (TCP/RTU) can be used either as a server component (if the connection is used by the MC’s server-side) or as a client component (if the connection is used by the MC’s client-side).
  • Each component has its own parameters that defines it.
  • When the MC acts as a server, all server components share the same memory address space, thus acting as one server with multiple connections.
  • Each server (slave) on a Modbus network has its own deviceID, which is a number between 1 and 247.

The Modbus server registers

  • There are 4 types of registers in the Modbus Server address space:
    1. Bits (1-bit registers)
    2. Input Bits (1-bit READ-ONLY registers)
    3. Holding Registers (16-bit registers)
    4. Input Registers (16-bit READ-ONLY registers)
  • Servers can read and write their own address space.
  • Clients can read and write a remote server’s address space.

 

Getting Started

In order to get started with Modbus features the following steps are required:

  1. Download the required files: Media:ModBus Required files new.zip
  2. Using the ControlStudio File Manager, Upload the following files to your MC as follows:
    1. Kill all tasks.
    2. In terminal, reset all tasks. 
    3. Add files.
    4. upload the appropriate files as follows:  
    • mb_x86.O (for softMC7 ) / mb_armA9.O (for softMC3) / MB_LEX.O (for softMC703) 
    • Modbus.lib  

5. Upload files to MC.

RTENOTITLE

1. Load the correct Object file (based on the controller type) and the Modbus library manually, by typing the following in the terminal:

Oload mb_x86.O/ Oload mb_armA9.O /Oload MB_LEX.O

 

Loadglobal Modbus.LIB

       That's it! You're now ready to configure the Modbus system.

Initializing the Modbus Environment

To initialize the Modbus environment, including the server address space, call:

?init_multi_server([bits],[input_bits],[holding registers],[input_registers])
  • The function prints "success" and returns 0 on success, or return an error code on failure.
  • Notice: You MUST call this method even if you only need Client components. In that case, just pass 0 as the required registers' size.
  • Notice: You can call this method only if there are no active server components.

Error codes:

Error Meaning
-1 Memory allocation failure.
-2 Some servers are still running and using an already mapped address space.
-3 Failed to create a modbus mapping.

Server Components

Adding server components

  • Each time you'll add a component, you will receive a handle, which is the component's identifier (for later use).
  • It is best to keep this handles in variables inside your program.

Creating a TCP server component

handle = mb_tcp_server_create([port],[deviceID])
  • This opens a TCP connection to the server on port [port] with deviceID [deviceID], and starts the created server immediately.
  • Returns a handle on success, or an error code on failure.

Error codes:

Error Meaning
-1 Server address spaces isn't initialized yet, please call "init_multi_server(...) and try again.
-2 Failed to create main socket.
-3 Failed to connect.
-4 Failed to create server thread.

Creating an RTU server component

handle = mb_rtu_server_create([type],[port],[baudrate],[data bits],[stop bits],[parity],[deviceID])
  • This opens an RTU connection with the given parameters, and starts the created server immediately.
  • Returns a handle on success, or an error code on failure.

Error codes:

Error Meaning
-1 Server address spaces isn't initialized yet, please call "init_multi_server(...) and try again.
-2 Invalid device string.
-3 Invalid parity.
-4 Failed opening RTU.
-5 Failed allocating query buffer memory.
-6 Failed to set RTU mode.
-7 Unable to connect.
-8 Failed to create server thread.
-9 The device is already in use by another system component.

Stopping Server Components

Stopping a specific server component

You can stop a specific server component by passing its handle to:

result = mb_server_stop([handle])
  • Given a handle, this will stop and free the memory of the appropriate server component.
  • Returns 0 on success, -1 on failure.

Stopping all server components

You can stop all server components with a single call to:

result = mb_server_stop_all

This function will:

  • Stop and free all server components.
  • Free the shared address space.
  • Return 0 on success, -1 on failure.

Client Components

Adding client components

  • Each time you'll add a component, you will receive a handle, which is the component's identifier (for later use).
  • It is best to keep this handles in variables inside your program.

Adding a TCP Client component

handle = mb_tcp_client_create([ip],[port])
  • This will opens a TCP connection to the client on the given ip and port, and start the client immediately.
  • Returns a handle on success, -1 on failure.

Adding an RTU Client component

handle = mb_rtu_client_create([type],[port],[baudrate],[data bits],[stop bits],[parity])
  • This will open an RTU connection to the client with the given parameters, and start the client immediately.
  • Returns a handle on success, -1 on failure.

Stopping client components

A specific client can be stopped by calling:

result = mb_client_stop([handle])
  • Given a handle, this will stop and free the memory of the appropriate client component.
  • Returns 0 on success, -1 on failure.

Reset the Modbus System

Sometimes, a user may wish to stop all server and client components at once, and reset the Modbus system (for example, when a user want to initialize a different Modbus system). To do that, call:

result = mb_reset

This function:

  • Stops all running servers and clients.
  • Frees their memory.
  • Frees the shared address space.
  • Reset the handle counter.
  • Returns 0 on success, -1 on failure.

Notice: This function is called automatically when calling reset all.

Reading and Writing

  • Servers can read and write their own address space.
  • Clients can read and write a remote server’s address space.
  • Therefore, Servers and clients use different functions to read/write data from the address space.

Server Components


Reading

  • The following functions read variables from the different types of registers and return them.
  • When a read error occurs, the functions will write [function name] + "ERROR" + [error code] in the Message Log.
Reading from Holding registers
Val = MB_SERVER_READ_REG_LONG([index], [byte_swap], [word_swap])
Val = MB_SERVER_READ_REG_SHORT([index], [byte_swap])
Val = MB_SERVER_READ_REG_FLOAT([index], [byte_swap], [word_swap])
Val = MB_SERVER_READ_REG_DOUBLE([index], [byte_swap], [word_swap], [long swap])
Reading from Bits registers
val = MB_SERVER_READ_BIT([index])
Reading from Input registers
Val = MB_SERVER_READ_INREG_LONG([index], [byte_swap], [word_swap])
Val = MB_SERVER_READ_INREG_SHORT([index], [byte_swap])
Val = MB_SERVER_READ_INREG_FLOAT([index], [byte_swap], [word_swap])
Val = MB_SERVER_READ_INREG_DOUBLE([index], [byte_swap], [word_swap], [long swap])
Reading from Input Bits registers
 val = MB_SERVER_READ_INBIT([index])
Valid Parameters
Parameter Valid Input
Index From 0 to the number of registers available.
Byte_swap 1 or 0 (True/False)
Word_swap 1 or 0 (True/False)
Long_swap 1 or 0 (True/False)

Writing

  • The following functions write data into the different types of registers.
  • When a write error occurs, the functions will write [function name] + "ERROR" + [error code] in the Message Log.
Writing to holding registers
Val = MB_SERVER_WRITE_REG_LONG([index],[new value],[byte swap], [word swap])
Val = MB_SERVER_WRITE_REG_SHORT([index],[new value],[byte swap])
Val = MB_SERVER_WRITE_REG_FLOAT([index],[new value],[byte swap], [word swap])
Val = MB_SERVER_WRITE_REG_DOUBLE([index],[new value],[byte swap], [word swap], [long swap])
Writing to Bits registers
val = MB_SERVER_WRITE_BIT([index],[new value])
Writing to Input registers
Val = MB_SERVER_WRITE_INREG_LONG([index],[new value],[byte swap], [word swap])
Val = MB_SERVER_WRITE_INREG_SHORT([index],[new value],[byte swap])
Val = MB_SERVER_WRITE_INREG_FLOAT([index],[new value],[byte swap], [word swap])
Val = MB_SERVER_WRITE_INREG_DOUBLE([index],[new value],[byte swap], [word swap], [long swap])
Writing to Input Bits registers
val = MB_SERVER_WRITE_INBIT([index],[value])
Valid Parameters
Parameter Valid Input
Index From 0 to the number of registers available.
New value The value to write, must be from the appropriate type.
Byte_swap 1 or 0 (True/False)
Word_swap 1 or 0 (True/False)
Long_swap 1 or 0 (True/False)

Error codes

Error Meaning
-1 Invalid index.
-2 Local server's address space isn't mapped yet.
-3 Failed to catch the register mutex.
-4 Failed to release the register mutex.

Client Components


Reading

  • The following functions read variables from the different types of registers in a REMOTE modbus server.
  • The read value is inserted into an existing variable from the appropriate type (long/double).
  • The functions return 0 on success or an error code (not 0) on failure.
Reading from Holding registers
Val = MB_CLIENT_READ_REG_LONG([handle],[deviceID],[addr],[dest ptr])
Val = MB_CLIENT_READ_REG_SHORT([handle],[deviceID],[addr],[dest ptr])
Val = MB_CLIENT_READ_REG_FLOAT([handle],[deviceID],[addr],[dest ptr])
Val = MB_CLIENT_READ_REG_DOUBLE([handle],[deviceID],[addr],[dest ptr])
Reading from Bits registers
val = MB_CLIENT_READ_BITS ([handle],[deviceID],[addr],[num of bits],[dest arr ptr])
Reading from Input registers
Val = MB_CLIENT_READ_INREG_LONG ([handle],[deviceID],[addr],[dest ptr]) 
Val = MB_CLIENT_READ_INREG_SHORT([handle],[deviceID],[addr],[dest ptr])
Val = MB_CLIENT_READ_INREG_FLOAT([handle],[deviceID],[addr],[dest ptr])
Val = MB_CLIENT_READ_INREG_DOUBLE([handle],[deviceID],[addr],[dest ptr])
Reading from Input Bits registers
val = MB_CLIENT_READ_INBITS ([handle],[deviceID],[addr],[num of bits],[dest arr ptr])
Valid Parameters
Parameter Valid Input
Handle The client's unique identifier (received on client creation).
DeviceID The remote server(slave)'s device ID.
Addr The index of the register to read from.
Num of bits (Reading bits) The number of bits to read.
dest ptr / dest arr ptr The variable to store the read data. When reading bits, this must be an array of longs in the appropriate size (>= Num of bits).

Writing

  • The following functions write data from existing variables to the different types of registers in a REMOTE modbus server.
  • The functions return 0 on success or an error code (not 0) on failure.
Writing to Holding registers
Val = MB_CLIENT_WRITE_REG_LONG([handle],[deviceID],[addr],[src ptr])
Val = MB_CLIENT_WRITE_REG_SHORT([handle],[deviceID],[addr],[src ptr])
Val = MB_CLIENT_WRITE_REG_FLOAT([handle],[deviceID],[addr],[src ptr])
Val = MB_CLIENT_WRITE_REG_DOUBLE([handle],[deviceID],[addr],[src ptr])
Writing to Bits registers
val = MB_CLIENT_WRITE_BIT([handle],[deviceID],[addr],[src ptr])
Valid Parameters
Parameter Valid Input
Handle The client's unique identifier (received on client creation).
DeviceID The remote server(slave)'s device ID.
Addr The index of the register to start writing to.
src ptr The variable that stores the data to be written. This must be a variable from the appropriate type.

Reading and Writing Summary

modbus;newAPI-readwriteSummary.jpg

Modbus Configurator

Background

General

The Modbus Communication Scripts Generator (Modbus Configurator) is a tool that allows you to map your softMC application variables to Modbus tags.

Note: Tag access is defined from the HMI perspective. In other words:

  • Read Access variables are written by the softMC to the Modbus address space.
  • Write Access variables are read by the softMC from the Modbus address space.

You can define whether a variable has Read Access (meaning it is read by the HMI/PLC), or Write Access (meaning it is written by the HMI/PLC). Currently, it is not possible to define a variable as having both Read Access and Write Access. However, all Write Access variables can be written once by the softMC upon system startup by a special routine that is generated in HMIMBMAP.LIB (see section below).

The MC MBConfigurator creates three files:

  • HMIMBMAP.LIB and HMIMBMAP.PRG files are MC-Basic scripts that are used to start a softMC task. These are default file names, which you can change, but must retain the 8.3 format. This task cyclically and indefinitely reads/writes Modbus tags according to access type.
  • A .CSV format file that can be used by an HMI development environment, such as JMobile Studio, Indusoft and HMIStudio, to automatically import Modbus tags. You define the HMI development environment by selecting various Python scripts that will generate the .csv file.

MBConfigurator setup

Note: Variables destined to be mapped to Modbus tags must be defined as global variables by the "Common Shared" declaration.

1. In order to map the variables, the program must be loaded in the softMC.

2. Start the Modbus Configuration. From the ControlStudio toolbar, select Tools > Modbus Configurator.

    The Modbus Configurator windows opens.

3. Select Connection > Connect.

The settings dialog box opens. Makes sure the correct MC IP and port are inserted:

RTENOTITLE

4. In the Modbus Configurator window select Modbus Comm. Settings. Choose "Generate a csv file to use with softMI". Make sure Refresh rate is 10ms or higher.

RTENOTITLE

 

5. In the Registers tab, enter the amount of registers needed per type.

  1. Notice: The maximum register number is 65536.

 

6. Select Connections, click Add and select TCP communication type with port number 502. 

RTENOTITLE

6. 

1. Once the Modbus Configurator is connected to softMC, a complete list of all the global variables will appear on the right side. Double-clicking on the variables will automatically map them to Modbus tags in consecutive order. The automatic Modbus address and data type are displayed in the table.

2. Veriable type can be changed by clicking on the register type. Bits are 1 bit registers. It can be used for triggering (Write) functions, such as enable/disable or reading various statuses (Read). Hregs are 16 bit registers which can be used for number input (Write), such as set velocity/position or reading values (Read), such as position feedback. 

If a mapped variable is defined as CONST, its access type is automatically set to Read. In such instances the access type cannot be changed. Read Access variables are read only by the HMI; therefore the softMC only writes them to the Modbus address space.

A variable that is not defined as CONST automatically appears as Write Access. Double-click on the access type to toggle the variable between Read Access and Write Access, and thus determine whether the variable will be read or written by softMC.

 

MB3onnection4.jpg

 

Generating and Using Scripts

After you are done mapping variables and defining the access types, a snapshot of the current configuration must be saved in order to generate the Modbus-handling scripts.

1. Click Files, and then Save As.

The mapping is saved in an .mbas file.
If you makes changes after saving the .mbas file, the MBAS file indicator in the status bar will light up.

2. To generate the product files, click Generate.

                      The Log windows will display Success messages.

                      3 files will be generated: HMIMBMAP.LIBHMIMBMAP.PRG, which will be used by the MC and STX_HMI.CSV, which will be used by the HMI program.

3. The defult location of the files generation is located in ControlStudio installation folder: C:\Program Files (x86)\Servotronix\MBConfigurator

 MBvonnection5.jpg

 

Using the Modbus-Handling Scripts

1. Using the ControlStudio, copy HMIMBMAP.LIB and HMIMBMAP.PRG to the softMC as shown in Media:ModBussetup.jpg

Note: Before these files can be loaded and used, your application(s), which include all the global veriables must be loaded (all mapped variables must exist in the softMC memory).

2. Using the ControlStudio Terminal, load the library HMIMBMAP.LIB:

Load HMIMBMAP.LIB
Since HMIMBMAP.PRG imports this library it must not be loaded globally. This code can be executed wherever is convenient.

3. Verify that the library was loaded successfully:

?tasklist

4. Start the Modbus communication task by loading the program:

Load HMIMBMAP.PRG

HMIMBMAP.PRG is defined as Program Continue, therefore it starts automatically after it is loaded and it does not require an explicit StartTask command.

Of course, HMIMBMAP.PRG can be loaded and executed only after HMIMBMAP.LIB is loaded. Therefore, you should add the following code to AUTOEXEC.PRG or wherever is convenient:

Load HMIMBMAP.LIB
Load HMIMBMAP.PRG

 

HMIMBMAP.PRG Explained

HMIMBMAP.PRG code:

import HMIMBMAP.LIB
Program Continue
	dim retVal as long = 0
	retVal = Init_Modbus
	while 1
		retVal = Read_Modbus_Registers
		retVal = Write_Modbus_Registers
		sleep 1
	end while
End Program

The functions Init_Modbus, Read_Modbus_Registers and Write_Modbus_Registers are implemented in HMIMBMAP.LIB, which is automatically generated by a Python script.

The function Init_Modbus starts the Modbus server and then writes to the Modbus address space all the Write Access Variables (i.e., all the variables read by the softMC from the Modbus address space). This feature allows you to setup the system to start with an initialized Modbus address space before the HMI/PLC connects to it. The HMI/PLC can read the address space and initialize itself accordingly.

The functions Read_Modbus_Registers and Write_Modbus_Registers are invoked cyclically and indefinitely. Read_Modbus_Registers reads all the tags that are written by the HMI/PLC and updates the Write Access variables with new values, while Write_Modbus_Registers does the opposite.

HMI IDEs and .CSV Files

Each line in the .csv file generated by the MCMBConfigurator file holds data about a single variable, such as Modbus address or data type.

This data can be used by an HMI IDE to import Modbus tags and associate them with HMI functionality.

Different manufacturer IDEs use different .csv formatting; therefore, various Python scripts are used to create the specific .csv files suitable for a particular manufacturer IDE.

HMI Programs

Note: HMI Studio is the most commonly used program.